iDM TERRA SW 50 Max H

The iDM TERRA SW 50 Max H is a heat pump with SCOP (35 °C) 6.37, refrigerant R134A and max. flow temperature 70 °C.1,2
Key figures
Rules in the UK
Boiler Upgrade Scheme
Not eligibleFixed grant in England and Wales, deducted from your installer’s quote. £9,000 when replacing oil or LPG off the gas grid (until March 2027). Scotland: Home Energy Scotland grant instead.4,5
- Must be MCS-certified (product and installer). Check the Ofgem product eligibility list.
- Rated output 71.8 kW; the scheme covers systems up to 45 kW.
- SCOP at 55 °C: 4.88. The installed system needs a SCOP of at least 2.8 (MCS calculation).
Technical specifications
| General | |
|---|---|
| Type (source) | Water-to-water1 |
| Compressors | 21 |
| Capacity control | leistungsstufen1 |
| Performance | |
| Rated output 35 °C | 71.8 kW1 |
| Rated output 55 °C | 69 kW1 |
| Max. flow temperature | 70 °C2 |
| Efficiency | |
| SCOP (35 °C) | 6.371 |
| SCOP (55 °C) | 4.881 |
| Seasonal efficiency ηs 35 °C | 247 %1 |
| Seasonal efficiency ηs 55 °C | 187 %1 |
| Energy label 35 °C | A+++2 |
| Energy label 55 °C | A+++2 |
| Noise | |
| Indoor unit sound power | 63 dB(A)1 |
| Refrigerant | |
| Refrigerant | R134A1 |
| Refrigerant charge | 16 kg1 |
| Electrical | |
| Max. power input | 25.6 kW1 |
| Connectivity & smart | |
| SG Ready | Yes1 |
How it ranks
SCOP (35 °C): better than 53% of comparable models in our database (Heat pumps · Water-to-water · ≥ 14 kW; n = 65).
Rank 31 of 66
Compared with every model on VersusIndex in the same group with a known value; equal values do not count as better. This says nothing about price, installation or reliability.
Manufacturer documentation
- Product page
- Brochure / leaflet — TERRA SW MAX H – Brochure
External links to iDM's official website. The manufacturer may change or move documents; where they differ, the manufacturer's latest version applies.
Similar models
Other brands, same type and a comparable size.
More from iDM
- iDM TERRA SW 50 MAX H 513 SCOP (35 °C): 5.96
- iDM TERRA SW 55 Max SCOP (35 °C): 6.55
- iDM TERRA SW 42 Twin SCOP (35 °C): 7.11
- iDM TERRA SW 35 Max H SCOP (35 °C): 6.61
- iDM TERRA SW 35 Twin SCOP (35 °C): 7.45
- iDM AERO ALM 10-50 Max SCOP (35 °C): 5.08
Guides on heat pumps
- SCOP, COP and ηs: what a heat pump’s efficiency figures mean
- Hybrid or full heat pump? The main types compared
- Heat pump noise: MCS 020(a), permitted development and where to put the unit
- Sizing a heat pump: heat loss, flow temperature and rated output
- Heat pump refrigerants: R290, R32 and R410A compared
How we collect and check this data →
Frequently asked questions
Sources
- List of eligible heat pumps (BEG) — Bundesamt für Wirtschaft und Ausfuhrkontrolle (BAFA) · accessed 18 Oct 2026
- Manufacturer data · accessed 21 Oct 2026
- Boiler Upgrade Scheme: what you can get — GOV.UK · accessed 27 Sept 2026
- Boiler Upgrade Scheme: guidance for installers (V5) — Ofgem · accessed 27 Sept 2026
- Boiler Upgrade Scheme product eligibility — Ofgem · accessed 27 Sept 2026