Waterkotte Industrial Line 5070.8 DT
The Waterkotte Industrial Line 5070.8 DT is a heat pump with SCOP (35 °C) 5.93 and refrigerant R513A.1
Key figures
Rules in the UK
Boiler Upgrade Scheme
Not eligibleFixed grant in England and Wales, deducted from your installer’s quote. £9,000 when replacing oil or LPG off the gas grid (until March 2027). Scotland: Home Energy Scotland grant instead.3,4
- Must be MCS-certified (product and installer). Check the Ofgem product eligibility list.
- Rated output 64.15 kW; the scheme covers systems up to 45 kW.
- SCOP at 55 °C: 4.7. The installed system needs a SCOP of at least 2.8 (MCS calculation).
Technical specifications
| General | |
|---|---|
| Type (source) | Water-to-water1 |
| Compressors | 41 |
| Capacity control | leistungsstufen1 |
| Performance | |
| Rated output 35 °C | 64.15 kW1 |
| Rated output 55 °C | 59.25 kW1 |
| Efficiency | |
| SCOP (35 °C) | 5.931 |
| SCOP (55 °C) | 4.71 |
| Seasonal efficiency ηs 35 °C | 229 %1 |
| Seasonal efficiency ηs 55 °C | 180 %1 |
| Noise | |
| Indoor unit sound power | 59 dB(A)1 |
| Refrigerant | |
| Refrigerant | R513A1 |
| Refrigerant charge | 2.7 kg1 |
| Electrical | |
| Max. power input | 26.8 kW1 |
| Connectivity & smart | |
| SG Ready | Yes1 |
How it ranks
SCOP (35 °C): better than 29% of comparable models in our database (Heat pumps · Water-to-water · ≥ 14 kW; n = 65).
Rank 46 of 66
Compared with every model on VersusIndex in the same group with a known value; equal values do not count as better. This says nothing about price, installation or reliability.
Similar models
Other brands, same type and a comparable size.
More from Waterkotte
- Waterkotte Industrial Line Air Kaskade 5072.6 SCOP (35 °C): 4.8
- Waterkotte Industrial Line 8060.7 (W/W) SCOP (35 °C): 7.81
- Waterkotte Industrial Line 5060.8 DT SCOP (35 °C): 6.27
- Waterkotte EcoTouch Air Kaskade 5090.5 SCOP (35 °C): 4.83
- Waterkotte Industrial Line Air Kaskade 5064.6 SCOP (35 °C): 4.8
- Waterkotte Industrial Line Air Kaskade 5056.6 SCOP (35 °C): 4.8
Guides on heat pumps
- SCOP, COP and ηs: what a heat pump’s efficiency figures mean
- Hybrid or full heat pump? The main types compared
- Heat pump noise: MCS 020(a), permitted development and where to put the unit
- Sizing a heat pump: heat loss, flow temperature and rated output
- Heat pump refrigerants: R290, R32 and R410A compared
How we collect and check this data →
Frequently asked questions
What is the SCOP (35 °C) of the Waterkotte Industrial Line 5070.8 DT?
The SCOP (35 °C) of the Waterkotte Industrial Line 5070.8 DT is 5.93.1
Which refrigerant does the Waterkotte Industrial Line 5070.8 DT use?
The refrigerant of the Waterkotte Industrial Line 5070.8 DT is R513A.1
How much Boiler Upgrade Scheme grant can you get for the Waterkotte Industrial Line 5070.8 DT?
Probably none. Rated output 64.15 kW; the scheme covers systems up to 45 kW.1