The Teon T60 Water is a heat pump with SCOP (35 °C) 4.45 and refrigerant R600A.1
Key figures
UK
Rules in the UK
Boiler Upgrade Scheme
Not eligibleFixed grant in England and Wales, deducted from your installer’s quote. £9,000 when replacing oil or LPG off the gas grid (until March 2027). Scotland: Home Energy Scotland grant instead.3,4
- Must be MCS-certified (product and installer). Check the Ofgem product eligibility list.
- Rated output 54.4 kW; the scheme covers systems up to 45 kW.
- SCOP at 55 °C: 3.31. The installed system needs a SCOP of at least 2.8 (MCS calculation).
Technical specifications
| General | |
|---|---|
| Type (source) | Water-to-water1 |
| Performance | |
| Rated output 35 °C | 54.4 kW1 |
| Rated output 55 °C | 50.08 kW1 |
| Efficiency | |
| SCOP (35 °C) | 4.451 |
| SCOP (55 °C) | 3.311 |
| Seasonal efficiency ηs 35 °C | 170 %1 |
| Seasonal efficiency ηs 55 °C | 124 %1 |
| Energy label 35 °C | A, , 1 |
| Energy label 55 °C | A, 1 |
| Noise | |
| Indoor unit sound power | 69 dB(A)1 |
| Refrigerant | |
| Refrigerant | R600A1 |
| Refrigerant GWP | 31 |
| Refrigerant charge | 4.51 kg1 |
Manufacturer documentation
- Datasheet / specifications — TEON BV – Technische data voor water/water uitvoering
External links to Teon's official website. The manufacturer may change or move documents; where they differ, the manufacturer's latest version applies.
Frequently asked questions
What is the SCOP (35 °C) of the Teon T60 Water?
The SCOP (35 °C) of the Teon T60 Water is 4.45.1
Which refrigerant does the Teon T60 Water use?
The refrigerant of the Teon T60 Water is R600A.1
How much Boiler Upgrade Scheme grant can you get for the Teon T60 Water?
Probably none. Rated output 54.4 kW; the scheme covers systems up to 45 kW.1
Sources
- Heat Pump Keymark certificates — EHPA / DIN CERTCO (Heat Pump KEYMARK) · accessed 29 Sept 2026
- Boiler Upgrade Scheme: what you can get — GOV.UK · accessed 27 Sept 2026
- Boiler Upgrade Scheme: guidance for installers (V5) — Ofgem · accessed 27 Sept 2026