The Carrier 61AQ070P is an air-to-water heat pump with a SCOP of 4.29 (35 °C) and a sound power level of 70 dB(A). Under permitted development the limit is 42 dB(A) measured 1 m from the nearest neighbouring habitable-room window. Free-standing, the indicative minimum distance is 10.0 m; against a wall 14.2 m.

Last updated: Technical specifications Rules in the UK

Key figures

SCOP (35 °C)
4.29

Seasonal efficiency: how much heat you get per kWh of electricity across a heating season.

Outdoor unit sound power
70dB(A)
Official source
Refrigerant
R290
Official source
Rated output 35 °C
62.5kW
Official source
Rated output 55 °C
62.5kW
Official source
UK

Rules in the UK

These rules are still being verified.

Minimum distance to your neighbour

Permitted development rights + MCS 020 planning standard · 1 m from the nearest neighbouring habitable-room window

Permitted development (MCS 020) ≤ 42 dB(A) · at the assessment position
Free-standing 10 m
Against wall 14.2 m
In corner 20 m

Indicative calculation (hemispherical, no barriers). Not a substitute for an MCS 020 assessment. Source

Boiler Upgrade Scheme

Unknown

Fixed grant towards installation; check current amount with Ofgem. Ofgem

Technical specifications

General
Type Air-to-water BAFA
Compressors 1 BAFA
Capacity control Inverter BAFA
Performance
Rated output 35 °C 62.5 kW BAFA
Rated output 55 °C 62.5 kW BAFA
Efficiency
SCOP (35 °C) 4.29 BAFA
SCOP (55 °C) 3.43 BAFA
Seasonal efficiency ηs 35 °C 169 % BAFA
Seasonal efficiency ηs 55 °C 134 % BAFA
COP A7/W35 3.98 BAFA
COP A2/W35 2.65 BAFA
COP A-7/W35 2.55 BAFA
SEER (cooling) 4.3 BAFA
Noise
Outdoor unit sound power 70 dB(A) BAFA
Indoor unit sound power 70 dB(A) BAFA
Refrigerant
Refrigerant R290 BAFA
Refrigerant GWP 3 RVO ISDE list
Refrigerant charge 3.9 kg BAFA
Connectivity & smart
SG Ready Yes BAFA

Frequently asked questions

Can I install the Carrier 61AQ070P without planning permission?

Under Permitted development rights + MCS 020 planning standard the unit must not exceed 42 dB(A) 1 m from the nearest neighbouring habitable-room window. With a sound power of 70 dB(A) that indicatively means 10.0 m free-standing, 14.2 m against a wall or 20.0 m in a corner. Your MCS installer must confirm this.

Which refrigerant does the Carrier 61AQ070P use?

The Carrier 61AQ070P uses R290.