Heat pumps · IE

STIEBEL ELTRON LWZ 07.1 Premium HKL 230

STIEBEL ELTRON LWZ 07.1 Premium HKL 230
Image: STIEBEL ELTRONrequest removal

The STIEBEL ELTRON LWZ 07.1 Premium HKL 230 is an air-to-water heat pump with a SCOP of 4.2 (35 °C) and a sound power level of 56 dB(A). In Ireland a heat pump is exempt from planning permission if it stays below 43 dB(A) (or 5 dB(A) above background noise, if higher), measured at the nearest neighbouring inhabited dwelling. Free-standing, the indicative minimum distance is 1.8 m; against a wall 2.5 m.1,2,3,4

Key figures

SCOP (35 °C)
4.24

Seasonal efficiency: how much heat you get per kWh of electricity across a heating season.

Heating capacity (A7/W35)
2.71kW3
Official source
Outdoor unit sound power
56dB(A)4
Official source
Refrigerant
R2901
Official source
Type (source)
Air-to-water1
Official source
IE

Rules in Ireland

Minimum distance to your neighbour

Planning and Development (Exempted Development) Regulations 2026 (S.I. No. 342 of 2026)5 · nearest neighbouring inhabited dwelling

Planning exemption: max 43 dB(A), or 5 dB(A) above background noise if higher≤ 43 dB(A) · normal operation
Free-standing1.8 m
Against wall2.5 m
In corner3.6 m

Indicative calculation (hemispherical, no barriers). Your installer must confirm the noise level at the nearest neighbouring dwelling.

SEAI Heat Pump System Grant

Check conditions

€14,5006Maximum for a house, incl. €2,000 boiler scrappage

Up to €14,500 for a house (€11,500 for an apartment), including a €2,000 boiler scrappage grant when an oil, gas, solid-fuel or storage-heater system is removed. Homes built before 2007 need a technical assessment (€200 grant) unless the BER shows a Heat Loss Indicator of 2.3 or less. Installation is charged at 9% VAT.7

  • The heat pump must be listed on SEAI's Home Appliance Register of Performance (HARP) and installed by an SEAI-registered contractor.
  • Home built and occupied before 2021, with an MPRN; grant approval before any work starts and a BER assessment afterwards.

Heat pumps: grants and rules in Ireland →

Technical specifications

General
Type (source)Air-to-water1
Compressors11
Capacity controlInverter1
Performance
Heating capacity (A7/W35)2.71 kW3
Rated output 35 °C7 kW4
Rated output 55 °C7 kW4
Efficiency
SCOP (35 °C)4.24
SCOP (55 °C)3.284
Seasonal efficiency ηs 35 °C165 %4
Seasonal efficiency ηs 55 °C128 %4
Energy label 35 °CA++4
Energy label 55 °CA++4
COP A7/W355.771
COP A2/W353.971
COP A-7/W352.711
Noise
Outdoor unit sound power56 dB(A)4
Indoor unit sound power51 dB(A)4
Refrigerant
RefrigerantR2901
Refrigerant GWP33
Refrigerant charge1.24 kg1
Electrical
Max. power input12.55 kW1
Connectivity & smart
SG ReadyYes1
Grants & market
ISDE grant (NL)2,375 €2

How it ranks

SCOP (35 °C): better than 4% of comparable models in our database (Heat pumps · Air-to-water · 6–8 kW; n = 175).

Rank 165 of 176

Compared with every model on VersusIndex in the same group with a known value; equal values do not count as better. This says nothing about price, installation or reliability.

Variants

This model is registered in 2 combinations (for example with a different indoor unit or cylinder) with exactly the same performance. All figures on this page apply to each of these types. The part of the type number that differs is in bold; small differences (e.g. cylinder volume or anode) are listed after it:

  • LWZ 07.1 Premium HKL 230
  • LWZ 07.1 Premium HKWL 230 — Indoor unit sound power: 53 dB(A)

Manufacturer documentation

External links to STIEBEL ELTRON's official website. The manufacturer may change or move documents; where they differ, the manufacturer's latest version applies.

Compare with

Similar models

Other brands, same type and a comparable size.

More from STIEBEL ELTRON

All STIEBEL ELTRON models (70) →

How we collect and check this data →

Frequently asked questions

Do I need planning permission for the STIEBEL ELTRON LWZ 07.1 Premium HKL 230 in Ireland?

Not if it meets the exempted-development conditions (Planning and Development (Exempted Development) Regulations 2026 (S.I. No. 342 of 2026)): no more than 43 dB(A) at the nearest neighbouring inhabited dwelling, or 5 dB(A) above background noise if that is higher. With a sound power of 56 dB(A) that indicatively means 1.8 m free-standing, 2.5 m against a wall or 3.6 m in a corner. Ask your SEAI-registered installer to confirm.1,2,3,4

How much SEAI grant can you get for the STIEBEL ELTRON LWZ 07.1 Premium HKL 230?

Up to €14,500 with the SEAI Heat Pump System Grant, including €2,000 boiler scrappage when an oil, gas, solid-fuel or storage-heater system is removed (€11,500 for an apartment). The home must be built and occupied before 2021, the heat pump must be on SEAI's HARP register and you need grant approval before work starts.1,2,3,4

Which refrigerant does the STIEBEL ELTRON LWZ 07.1 Premium HKL 230 use?

The STIEBEL ELTRON LWZ 07.1 Premium HKL 230 uses R290.1,2,3,4

Sources

  1. List of eligible heat pumps (BEG) — Bundesamt für Wirtschaft und Ausfuhrkontrolle (BAFA) · accessed 27 Sept 2026
  2. ISDE heat pump notification code list — Rijksdienst voor Ondernemend Nederland (RVO) · accessed 28 Sept 2026
  3. Heat Pump Keymark certificates — EHPA / DIN CERTCO (Heat Pump KEYMARK) · accessed 29 Sept 2026
  4. European Product Registry for Energy Labelling (EPREL) – heat pumps — Europese Commissie · accessed 15 Oct 2026
  5. Planning and Development (Exempted Development) Regulations 2026 (S.I. No. 342 of 2026)
  6. Heat Pump System Grants — SEAI · accessed 4 Oct 2026
  7. Heat pump heating system (VAT) — Revenue · accessed 4 Oct 2026