Heat pumps · UK

Daikin Airconditioning GermanyEWYK060CZN-A2

The Daikin Airconditioning Germany EWYK060CZN-A2 is an air-to-water heat pump with a SCOP of 4.38 (35 °C) and a sound power level of 71 dB(A). Under permitted development the limit is 42 dB(A) measured 1 m from the nearest neighbouring habitable-room window. Free-standing, the indicative minimum distance is 11.2 m; against a wall 15.9 m.

Last updated: Technical specifications Rules in the UK

Key figures

SCOP (35 °C)
4.38

Seasonal efficiency: how much heat you get per kWh of electricity across a heating season.

Outdoor unit sound power
71dB(A)
Official source
Refrigerant
R290
Official source
Rated output 35 °C
38.88kW
Official source
Rated output 55 °C
39.15kW
Official source
UK

Rules in the UK

These rules are still being verified.

Minimum distance to your neighbour

Permitted development rights + MCS 020 planning standard · 1 m from the nearest neighbouring habitable-room window

Permitted development (MCS 020) ≤ 42 dB(A) · at the assessment position
Free-standing 11.2 m
Against wall 15.9 m
In corner 22.5 m

Indicative calculation (hemispherical, no barriers). Not a substitute for an MCS 020 assessment. Source

Boiler Upgrade Scheme

Unknown

Fixed grant towards installation; check current amount with Ofgem. Ofgem

Technical specifications

General
Type Air-to-water BAFA
Compressors 2 BAFA
Capacity control Inverter BAFA
Performance
Rated output 35 °C 38.88 kW BAFA
Rated output 55 °C 39.15 kW BAFA
Efficiency
SCOP (35 °C) 4.38 BAFA
SCOP (55 °C) 3.39 BAFA
Seasonal efficiency ηs 35 °C 172.2 % BAFA
Seasonal efficiency ηs 55 °C 132.6 % BAFA
COP A7/W35 4.4 BAFA
COP A2/W35 3.9 BAFA
COP A-7/W35 3.15 BAFA
SEER (cooling) 5 BAFA
Noise
Outdoor unit sound power 71 dB(A) BAFA
Refrigerant
Refrigerant R290 BAFA
Refrigerant charge 5.9 kg BAFA
Electrical
Max. power input 16.19 kW BAFA
Connectivity & smart
SG Ready Yes BAFA

Frequently asked questions

Can I install the Daikin Airconditioning Germany EWYK060CZN-A2 without planning permission?

Under Permitted development rights + MCS 020 planning standard the unit must not exceed 42 dB(A) 1 m from the nearest neighbouring habitable-room window. With a sound power of 71 dB(A) that indicatively means 11.2 m free-standing, 15.9 m against a wall or 22.5 m in a corner. Your MCS installer must confirm this.

Which refrigerant does the Daikin Airconditioning Germany EWYK060CZN-A2 use?

The Daikin Airconditioning Germany EWYK060CZN-A2 uses R290.